Home › News & tips

What your annual fire alarm inspection checks

fire-alarm-checklist

Your fire alarm has two jobs: notice a fire early, and tell everyone in the building to get out. The annual inspection proves it can still do both.

Why the alarm is tested every year

A fire alarm system sits quiet almost all the time. Detectors collect dust, batteries age, and a renovation can put a new wall between a horn and the people it's meant to wake. None of that shows on the panel until someone tests it.

What the code requires

Article 6.3.1.2 of the National Fire Code of Canada 2020 says fire alarm systems must be inspected and tested in conformance with CAN/ULC-S536, Standard for Inspection and Testing of Fire Alarm Systems. Alberta's 2023 edition uses the same article, and the codes in Saskatchewan, Manitoba and British Columbia are based on the national one.

CAN/ULC-S536 sets an inspection and test of the whole system every year, plus shorter daily and monthly checks between visits. The same article says every part of the system must stay accessible for inspection.

What happens during the inspection

  • The technician checks the control panel, its batteries and the charger.
  • Every manual pull station is operated.
  • Every smoke and heat detector is tested, and smoke detectors are checked for sensitivity where the standard calls for it.
  • Horns, bells and strobes are checked on every floor, so the alarm reaches everyone.
  • The signal to your monitoring company is tested from start to finish.

You get a report that lists each device and its result. Anything that doesn't meet the standard is listed as a deficiency, with a quote to fix it.

What you can do before the visit

  1. Find your last report and the log book.
  2. Tell tenants the date, and arrange access to suites that have devices inside.
  3. Clear storage away from the panel and the pull stations.
  4. Tell us about renovations since the last test. A new wall or ceiling can mean a device needs to move.

Questions

Will the alarm sound all day? It sounds in short bursts while devices are tested. We tell your monitoring company before we start and again when we finish.

Do you need to get into every unit? Only units with devices inside, such as heat detectors or speakers. We give notice so tenants can plan.

What are the daily and monthly checks? They're set out in CAN/ULC-S536 and recorded in your log book. Your annual report shows which ones apply to your system.

What happens if something fails? It's listed as a deficiency with a quote. Accept the quote, and the same tracking number follows the repair.

Book your annual fire alarm inspection online, and your request goes to the member that serves your city.

Call 1-833-344-3473, email service@firecanada.ca or visit www.firecanada.ca.

Source: National Fire Code of Canada 2020, Article 6.3.1.2; CAN/ULC-S536:2019.


Book it with your local member

Request service online and your request goes to the member that serves your city. Ask now, hear back by the next business day.