When someone needs an extinguisher, it has to work. The fire code sets four different checks to make sure it does, and one of them is yours.

What the code requires

Article 6.2.1.1 of the National Fire Code of Canada 2020 says portable extinguishers must be inspected, tested and maintained in conformance with NFPA 10, Standard for Portable Fire Extinguishers. NFPA 10 sets four intervals:

CheckHow oftenWho does it
InspectionAt least once each calendar monthYou or your staff
MaintenanceEvery yearA trained technician
6-year maintenanceEvery 6 years, on stored-pressure units with a 12-year hydrostatic testA trained technician
Hydrostatic testEvery 5 or 12 years, depending on the typeA trained technician

A hydrostatic test pressure-tests the shell to make sure it can still hold pressure. Water, foam, wet chemical and carbon dioxide units are tested every 5 years. Most dry chemical units with steel or aluminum shells are tested every 12 years.

The monthly inspection is yours

Once a month, someone in the building checks every extinguisher. It takes a few seconds each:

  1. It's in its place, and nothing blocks it or hides it.
  2. The gauge needle is in the green.
  3. The pin and the tamper seal are in place.
  4. There's no damage, corrosion or leaking.
  5. Initial and date the tag.

If any of these fail, take it out of service and call us.

What the annual visit covers

The technician examines each unit, inside and out where the standard calls for it, and puts on a new tag. When a unit is due for its 6-year maintenance or its hydrostatic test, it's done or replaced on the same visit. The technician also checks that you have the right type for each hazard, including a Class K unit in commercial kitchens.

Questions

Is the tag enough proof? The tag shows the last annual maintenance. Keep the monthly initials on it too; they're your record of the monthly inspection.

Should we repair or replace an old unit? It depends on the type and the cost of the test against a new unit. The technician gives you both prices.

Can we refill it ourselves after use? No. Any extinguisher that's been used goes back to a technician for recharge.

Book your extinguisher service online, and your request goes to the member that serves your city.

Call 1-833-344-3473, email service@firecanada.ca or visit www.firecanada.ca.

Source: National Fire Code of Canada 2020, Article 6.2.1.1; NFPA 10.