A sprinkler system may never open a single head, and it still has to work the first time it's needed. Regular inspection is how you know it will.
What the code requires
Article 6.4.1.1 of the National Fire Code of Canada 2020 says water-based fire protection systems must be inspected, tested and maintained in conformance with NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems. NFPA 25 makes the property owner responsible for having that work done, by qualified people.
The standard sets a full inspection and test every year. In between, gauges, valves and alarm devices are checked every quarter. Every 5 years, the inside of the piping is checked for blockages, and gauges are replaced or tested against a calibrated gauge.
What the technician checks
- Control valves are open and supervised, so a closed valve sends a signal to the panel.
- Sprinklers are free of paint, corrosion, damage and anything hanging from them. NFPA 25 calls for heads that show any of these to be replaced.
- The waterflow alarm is tested, so water moving in the pipes sets off the fire alarm.
- The main drain test shows whether the water supply is as strong as last year.
- Dry pipe and pre-action valves get their own trip tests on the schedule NFPA 25 sets.
What you can do between visits
- Keep storage at least 457 mm (18 in.) below the sprinklers. NFPA 25 calls for storage closer than the clearance rules allow to be corrected.
- Keep the heat on in every room with wet pipe. Frozen pipe can burst and leave that area without protection.
- Don't paint over sprinklers, and don't hang anything from them or from the pipe.
- Call us before closing any valve for renovation work. The fire code requires other measures to keep the building protected while a system is shut down.
Questions
A head was painted by mistake. Can it be cleaned? No. NFPA 25 calls for painted sprinklers to be replaced, because paint can stop the head from opening at the right temperature.
Will the inspection set off the alarm? The waterflow test does. We tell your monitoring company and your occupants first.
Do I need spare sprinklers? Yes. NFPA 25 checks the spare sprinkler cabinet every year for the right number and types, plus a wrench for each type.
Book your sprinkler inspection online, and your request goes to the member that serves your city.
Call 1-833-344-3473, email service@firecanada.ca or visit www.firecanada.ca.
Source: National Fire Code of Canada 2020, Articles 6.1.1.4 and 6.4.1.1; NFPA 25-2017.