What the fire code requires
Article 2.6.1.9 says commercial cooking fire protection systems must be inspected and maintained to NFPA 96, and wet chemical systems follow NFPA 17A, which calls for maintenance at least every 6 months and after any discharge. Instructions for working the system by hand must be posted in the kitchen.
Your local fire department has the final say for your building.
What the visit covers
- Nozzles aimed at the right appliances, with their blow-off caps on
- Detection links replaced as the manufacturer requires
- The pull station and gas shut-off tested
- Cylinder pressure and dates
- A check that the appliances underneath haven’t moved or changed
What you check between visits
The pull station is clear, and nothing has moved under the hood. If an appliance changes, book a check before you cook on it.
Repairs and deficiencies
Anything that doesn’t meet the standard is listed as a deficiency in your report, with a quote to fix it. The report and the quote look the same at every member. Accept the quote and the same tracking number follows the repair.