What the fire code requires
Article 6.5.1.6 says battery units must be inspected and tested every month, and tested every 12 months for their full design duration on a simulated power failure. Article 6.5.1.7 covers other emergency lights every 12 months.
Your local fire department has the final say for your building.
What the visit covers
- The full-duration test
- Battery condition, terminals and charging after the test
- Lamp heads aimed at the exit path
- A list of any units that failed
What you check between visits
Once a month, each battery unit’s pilot light is on and the lights come on when you press test. Record it.
Repairs and deficiencies
Anything that doesn’t meet the standard is listed as a deficiency in your report, with a quote to fix it. The report and the quote look the same at every member. Accept the quote and the same tracking number follows the repair.
Often in the same building: Exit signs · Fire alarm · All services
Source: National Fire Code of Canada 2020, Articles 6.5.1.6 and 6.5.1.7.